Thyros 60

Fire-rated doorset system. Side-hung 60-minute fire door leaf and frame.

Fire resistance level -/60/45

Structural / Integrity / Insulation (minutes)

The Thyros 60™ is a single, side-hung fire doorset engineered by Nexdor Systems and fire-tested by Jensen Hughes in accordance with AS 1530.4:2014 and AS 1905.1:2015. The composite door leaf, pressed-metal frame and sealing hardware achieve an FRL of -/60/45 across single- and dual-layer plasterboard, timber stud, insulated staggered-stud, concrete and masonry wall constructions.

Download the Thyros 60 spec sheet (PDF, Revision 3.0, 27 October 2026)

At a glance

  • Test standard: AS 1530.4:2014
  • Doorset standard: AS 1905.1:2015
  • Leaf thickness: 49 mm nominal
  • Fire tested by Jensen Hughes

Pair of fire doors in the test furnace at the Jensen Hughes fire testing laboratory, with the clock showing one hour
Fire test at the Jensen Hughes fire testing laboratory.

Door leaf

Maximum leaf size is 1020 mm wide by 2760 mm high, or 1173 mm wide by 2500 mm high. Height and width are inversely constrained: reducing width permits greater height. Oversize leaves are assessed in walls at least 144 mm thick (2 × 13 mm FR plasterboard or concrete/masonry). The tested leaf size is 2400 mm high × 1020 mm wide.

The base facing is MDF, 3–5 mm thick. An optional overlay of up to 1.5 mm can be bonded over the MDF on both sides, full height and width: timber veneer or timber facing, or steel sheet (for example Zincaneal or stainless steel).

Door frame

Pressed metal, welded and dressed, in 1.4–1.6 mm mild steel, with a single or double rebate. Fixing centres are a maximum of 400 mm for all fixing methods. Five fixing systems are approved, matched to the wall type: MS Strap, New Gen and Partition for stud walls, and Dynabolt and Wire Ties for concrete and masonry.

Walls and approved hardware

Approved wall constructions cover steel stud (single and dual layer), insulated staggered steel stud, timber stud, concrete and masonry, and lined concrete and masonry. The spec sheet lists the minimum thickness and FRL for each wall, and the approved door hardware with the fire test report for every item.

More hardware is being added through pilot fire tests, so always check that you have the latest revision of the spec sheet. Hardware that is not listed must be assessed by Jensen Hughes before use.

Questions about Thyros 60? Get in touch.